Function Code 22:
Reported Volume Decimal Point
0 = XXX.XXX***
1 = XXXX.XX (export only)
Function Code 24:
Hose Pressurization
0 = Off***
1 = 2 hours
2 = 1/2 hours
Note: Not available in U.S. gallons
configuration.
Command Code 12:
Pump Program
• Enter 12
• Enter Side #
1 = Side 1
2 = Side 2
• Enter Function Code (1-4)
• Enter Configuration Code
Function Code 1:
Two-Wire Pump ID
1-16 = (7*** for Side 1; 11*** for Side 2)
Function Code 3:
Side Exists
0 = Does not exist
1 = Exists***
Function Code 4:
PPU Options
0 = Level 1 price bar displays level
sent by console or Card Reader
IN Dispenser (CRIND
®
)***
1 = Normal
*** Default
† Must be programmed to ‘1’ in New
Jersey.
From Level 3
Command Code 13:
PIN Code Change
Press Enter after selections.
• Enter 13
• Enter Level # 1, 2, or 3
• Enter new PIN Code
Unit returns to Command Input Mode.
Command Code 15:
Function Code 1:
Preselect Time-Out
0 - 999 seconds
Function Code 2:
Pump Time Out
0 - 999 seconds
Function Code 3:
Beeper Time Out
0 - 999 seconds
Function Code 4:
Slowdown Valve
0 - 0.999 gallons
Command Code 17
Conversion Factor and Master
Reset
Select Function Code.
Function Code 1:
Conversion Factor
0 = No conversion factor***
1 = U.S. Gallons
2 = Imperial Gallons
3=Liters
Function Code 2:
Master Reset (Retains Totals)
0 = No Master Reset
1 = Master Reset
Command Code 18:
Pulse Output Configuration
• Enter 18
• Enter Function #
• Enter Configuration #
Function Code 1:
Volume PPU
1. 1 PPU
2. 10 PPU***
3. 50 PPU
4. 100 PPU
5. 1000 PPU
Function Code 2:
Volume Pulse Width
1. 0.5 ms
2. 1.0 ms
3. 2.0 ms
4. 4.0 ms***
5. 17.0 ms
6. 19.0 ms
7. 26.0 ms
8. 150.0 ms
Function Code 3:
Money Pulse Width
1. 0.5 ms
2. 1.0 ms
3. 2.0 ms
4. 4.0 ms***
5. 17.0 ms
6. 19.0 ms
7. 26.0 ms
Function Code 4:
Volume Suppression (at start of
sale)
1. 0.030***
2. 0.009
3. 0.000
Function Code 5:
Quadrature Pulse Option
0 = Disabled***
1=Enabled
Function Code 6:
Authorize After Pump Stop
0 = Disabled***
1=Enabled
Function Code 7:
Price Restore Option
0 = Disabled***
1=Enabled
*** Default
ATC Programming
• Turn ON the programming switch on
the ATC Controller board.
• Press 100 then Enter.
• Select Fuel Type and press Enter.
740 = Gasoline
840 = Diesel
730 = Default
• Firmware cycles through each
fueling position. Select Fuel Type
and press Enter.
• Turn OFF the programming switch
on the ATC Controller board.
• Press F2 to exit ATC Programming
Mode.
ATC Inspection
Modes
• From Manager Keypad, press an
ATC Function Code (see below)
when unit is idle.
• Press Enter and Meter Number, if
appropriate.
• Press F1 to exit ATC Inspection
Mode.
Function Code 200:
Real Time Transaction Mode
• Main Display = Gross Volume
• Volume Display = Net Volume
• Grade 1 PPU Display = Current
Temperature
Function Code 300:
Audit Last Transaction
• Main Display = Gross Volume
• Volume Display = Net Volume
• Grade 1 PPU Display = Average
Temperature
Function Code 301:
Display Volume Correction Factor
• Main Display = Meter Number
• Grade 1 PPU Display = Volume
Correction Factor
Function Code 302:
Display Fuel Density
• Main Display = Meter Number
• Grade 1 PPU Display = 730 Gas or
840 Diesel
Function Code 303:Display
Temperature
• Main Display = Meter Number
• Grade 1 PPU Display = Current
Temperatur e
Function Code 304:
Display Gross Totals
• Volume Display = Gross Volume
(most significant)
• Grade 1 PPU Display = Gross
Volume (least significant)
Function Code 500:
Display Software Version
Main Display = ATC Version
Error Codes
Code Description
20 Pulser Fail
24
Conversion Factor Changed/Not
Programmed
25
Two-Wire/Standalone Mode
Changed
26 Meter Not Calibrated
27 Side 1 Two-Wire ID Changed
28 Side 2 Two-Wire ID Changed
29 Pump Time-Out Error
31 Totals Data Error
32 Pulser Count Error
35 Configuration Data Error
36
Unit Type Configuration Code
Changed
37 PIN Code 1 Changed
38 PIN Code 2 Changed
39 Cash/Credit Option Changed
40 Master Reset Jumper in Place
41 Side Exists Option Changed
44 Pump Handle Up at Power Up
45 Preset Overrun (Minor)
46 Preset Overrun (Major)
Atlas
is a trademark of Gasboy
International. CRIND
®
is a registered
trademark of Gilbarco Inc.