MDE-5073 TopKAT™ PLUS Bypass Switch Installation Instructions · March 2013
Issues, Observation, and Suggestions
Following observation and suggestions have been made from reviewing the documentation
and field installation drawings from Orpak
™
for the optional Manual Override feature for the
TopKAT PLUS mechanical system.
Issues Observation Suggestions
Override/Bypass Switch is
recommended and shown to be
located in
the circuit breaker/sub
panel.
Due to location and distance of the circuit
b
reaker panel, and the requirement to run
the AC and DC in two separate conduits.
It is not suggested or recommended to
h
ave low vol
tage DC around or near high
voltage AC of the circuit breaker panel
which may/will place noise on the low
voltage line that may/will effect the
operation of the bypass feature not to
function properly.
• Place the Bypass Switch in a secured
exp
l
osion/weather proof enclosure on or
near the TopKAT PLUS or fuel island
following the National Electrical Code
(NEC) regulations, 18-inch off the
ground and 18-inch from a pump. Two
conduits must run to the enclosure.
• For kiosk located on or near the fuel
island, suggested applications can
be
installed and located in the pedestal,
above the 18-inch barrier plate of the
TopKAT PLUS.
The double pole switch contains
hig
h
AC voltage switch on one
pole and low DC voltage switch
on the other pole.